I had been having some major noise problems since I got a different laptop. I use an external USB Sound Blaster Live! soundcard when I use my laptop, and normally this resulted in amazing clarity -- wayyyyy better than onboard -- noticeably a lot better.

Since I switched from an older PIII Thinkpad to a Gateway laptop, I had noise problems. Not even when the USB was plugged in -- all it had to do was make contact with any metal on the chassis. Same for the onboard sound.

In addition, I noticed that the noise was only apparent when plugged into AC power. On battery it was perfect.

I had ruled out the power supply, and always used the same circuit. I even tried a different laptop (also gateway... maybe a problem here??) and had the same results.

On a hunch, I plugged the laptop power supply into a 3-prong adapter/cheater, and wallah: the noise was gone.

I think I actually yelled an audible cheer at the time :sqbiggrin:

Thought I would share so that others might benefit. This post was prompted by the other line noise post today -- this method can be used to test for ground loops in many types of equipment. Just remember: the ground plug is there for safety. Therefore it is not adviseable to run equipment that came with a 3 prong plug without the ground plug permanently. With a laptop, I'm not too worried about it, but with amps or other equipment you can find solutions online (google Ground Loop Isolator) that should preserve the safety aspect while also solving your problems.
 
On a hunch, I plugged the laptop power supply into a 3-prong adapter/cheater, and wallah: the noise was gone.
Do it the right way and buy a Ebtech Hum X filter. It safely gets rid of the hum without affecting the signal's volume or frequency response.

Voila!
 
AWDJ,
Hey brother. I had the same problem when I went digital. So, I posted over on another web board about how safe it was. The actual topic of my post was, "3 to 2 prong adapter, is it safe". Wow I got some responses.

Overall, I was told it was unsafe. I was also called a 3 prong "cheater". PM me and I will send you a link to the discussion, I think you'll find it interesting. Well here's one excerpt.

Originally Posted by SirWolfy

NFPA (National Fire Protection Agency) Statistics state that each year, a select few morons in the United States help to strengthen the human gene pool by eliminating themselves and / or their property through the improper or illegal use of gound-lifting devices. In 2002 alone, this has resulted in more than 12,000 incidents nationwide, causing 671 fatalities and more than $35,000,000 in property damages.

That dollar amount doesn't include the higher taxes to pay for the personel and equipment to respond to these emergencies or increased insurance rates because of the ones that couldn't even manage to kill themselves in the process or destroy homes or businesses in the course of the short-sighted antics. Then there's the additional burden on local economies because these retards destroy homes and businesses, requiring sparse resources from the Red Cross and other agencies to feed, clothe and shelter those that have been injured and / or left homeless as a direct result.

Anyway, the moral of the story is this; the next time you wanna gamble with your life, do so in a manner that will not effect someone else's life, livelyhood, home or business. Think past yourself for a change (I know this is a real challenge for some of you in the 3-prong cheater crowd) and take into consideration all of the people that will be affected when statistics finally catch up to you. You say you're a "professional"? I say start acting like one.

Some real food for thought...

I found it funny, because one of my laptops power adapter has only two prongs. My performance laptop just happens to have three. The post just made me snicker.

Groovielou
 
Groovielou, the grounding advice is obviously not meant for two-pronged plugs since they obviously do not have a ground prong.

The 3-to-2 prong adapters are what are referred to as "cheaters," as in "cheater plugs."

Also, understand that SirWolfy has a background in firefighting, so the response he gave would be completely expected.
 
I found it funny, because one of my laptops power adapter has only two prongs. My performance laptop just happens to have three. The post just made me snicker.

Groovielou


That's just it. I'm a CET and for a laptop, I wouldn't worry about it much, if at all. Low power plastic devices like desktop speakers, lamps, etc usually don't have the third prong.

I wouldn't run a power amp, drill, saw, etc on a cheater (not more than testing it anyway) or most other gear. Hell, most vacuums don't even have the third prong. My other laptop didn't have it either.

Don't get me wrong, they do add a degree of safety, and many devices require them. I just find the reply you quoted above great though. That applies more to the loaded-power-strip-extension-corded-around-the-room-into-a-cheater senario. ;)
 
Groovielou, the grounding advice is obviously not meant for two-pronged plugs since they obviously do not have a ground prong.

The 3-to-2 prong adapters are what are referred to as "cheaters," as in "cheater plugs."

Also, understand that SirWolfy has a background in firefighting, so the response he gave would be completely expected.

I think he was just saying that not all laptops even have the third prong, implying that they're probably not really all that necessary for a laptop. :sqconfused:
 
I guess it would depend on the design of a given laptop.

I was also called a 3 prong "cheater".
Please refer to the sentence in my post regarding cheaters. Need I say more?
 
Y'know, I just can't help but post this here :)

My house is 200+ years old, and my GrandPa did all the wiring. Fairly good job I might add.

When my Aunt died, and I came up to take care of Grandma, they had a Christmas Village setup in the old bar. It covered most of a 30 x 30' room, and included lit up houses, Christmas lights chained together, regular lamps, a fifties Coke machine, an ice cream cooler, lamps, etc.

There were 16 power strips, all loaded to the max, and plugged into one cheater, in one outlet :sqerr: :sqlaugh:

I myself, prefer DC ;)
 
Bryan,

Personally, I dont care if he was the president. Wolfy is a great guy, but I was taken a back when that was posted. I have respect for the man, thats why I didnt tear into him.

Moreover, he did make it clear that the post refrenced above was not tward me with this statement.

Lou,
That rant was actually aimed at a different group of folks about a year ago and was one of three I could easily find. I'm just in one of those phases where I am a bit persnickity with repeating myself ad naseum about 3-prong cheaters.

Groovielou
 
The Stats quoted have definite Validity. Having spent 6 Years as a Fire/Casualty Commercial Building Underwriter, and a career as a Broker in the Large Commercial Lines Property/Liability Insurance Biz. You need only see one fire as a result of a faulty ground, and how fast electrical fires spread throughout the circuit. After witnessing this you will not use the cheaters..............I have never used one for any connection......ever.......
 
Let's not get melodramatic

Look fellows, I'd never advise anyone to disregard the electrical codes. That said, IF you know what you're doing you can break rules without getting killed. Run a drill without a ground? Is it double insulated? Are you standing in a pool of water?

Ranges and free standing stoves traditionally never had grounds. The frame was attached to the neutral. Did homes spontaneously combust? No. Is it safer to have the frame attached to a redundant ground rather than a neutral? Yes.

Some time back I researched the claims made in that NFPA reference. I could find no statistics supporting the claim. I wrote the author and received no response (I can't confirm his receipt of my communication). There are tens of millions of people living in millions of homes that were built pre-ground requirement. Do insurance carriers require higher payments for life insurance covering the souls in these "death traps"? I too live in one. I sleep well.

Follow the code most especially if you don't know what you're doing. That said, don't get overwrought by the prospect of putting in a cheater for one night, if that gets you by for the evening. Just don't leave it that way. The NFPA writes the NEC (National Electrical Code). They've been at it for a long time and they are dealing with ever smaller statistical risks to make it continually safer to use electricity.

A cheater should not be a standard operating proceedure. Conversely, how in the world is lifting a ground connected to a plastic encased power supply connected to a plastic encased low voltage laptop going to cause the dire effects cited? Hook it up right boys but let's not not get melodramatic.

If anyone has backup for those fire statistics cited - I'd really like to read 'em. Thanks .